After a thunderstorm in late spring, the maintenance director walks the campus and finds that the camera on the detached garage is dead, the phone in the cottage is silent and a network switch in the main building has a port that no longer works. Nothing was struck directly. The damage arrived on a wire.
Any cable that leaves a building can carry an electrical surge back in with it. A good protection plan treats every outdoor cable as a possible path and gives the surge somewhere safe to go.
Lightning does not need to hit your building to cause damage. A strike nearby, on the ground, a tree or a utility pole, raises the electrical potential of the soil and of anything metal nearby. That energy couples into long conductors such as copper data cable, telephone lines, coax from an antenna or a satellite dish, and power lines.
The surge follows the metal. A long cable between two buildings works like an antenna and can pick up energy along its length. When it reaches equipment, the sudden rise in voltage can burn out a port, a power supply or a circuit board. Surges can also come from the power company's side and from large equipment switching on and off, not just storms.
Fiber optic cable made of glass with no metal in it does not conduct electricity, which is why it is commonly used between buildings. Some fiber cables include metal strength members or armor, so ask your installer which type you have.
Walk the property and list every cable that leaves the main building:
Copper data cable to a detached building or an outdoor camera.
Telephone lines, including those from the provider, and older alarm or elevator lines.
Coax for a rooftop antenna, a satellite dish or a cable internet connection.
Power circuits feeding outdoor equipment such as a gate operator, a parking lot light or a camera pole.
Antenna cables for wireless links between buildings.
Each is a path in. The weakest equipment on the path is often the first to fail, which may be a small, cheap device with an expensive consequence.
Surge protection is a set of layers, not a single gadget.
Use fiber where practical for links between buildings, since it breaks the electrical path. Convert to copper only where it ends.
Install data surge protectors designed for the cable type, placed where the cable enters the building and at the far device, and connected to a good ground.
Protect power as well as data. A protector on the data line does little if the device is also plugged into an unprotected outlet. Use surge protection on the power feed to the equipment, and keep power and data protectors grounded together.
Protect coax and antenna lines with protectors made for that purpose, installed at the point where the cable enters the building.
Keep cable runs short and low, and avoid routing them near lightning rods or tall poles where practical.
Protectors have a limited life. They absorb energy and wear out, so replacing them after a significant storm or on a schedule is sensible. Many have an indicator light, which should be checked.
A protector is only as good as its connection to ground. Its job is to divert the surge to the grounding system, so a long, thin or loose ground wire defeats it. Short, direct and tight connections to a common grounding point are the goal, and the grounding for power, data and antenna systems should be bonded together to the building's main grounding point. Otherwise the surge may find a path through your equipment between the two.
This is electrical work that is governed by local code, and it belongs with a qualified electrician. Your maintenance director can arrange it, and your IT provider can specify what each cable needs.
Have a short routine. Check for equipment that lost power or connection, look at the protectors' indicator lights, test the outdoor cameras and links, and note any new errors. Report unusual failures to your insurer's claims contact promptly, and keep records of the affected equipment, since coverage terms vary and you should confirm what your policy says.
When adding a new outdoor camera, wireless link or detached building, build protection into the budget from the start. Retrofitting after a loss is more expensive and less reliable.
UnityCare IT can survey your property for cables that leave the building, recommend the right protectors for each, and coordinate grounding work with your electrician. We also install and support outdoor cameras and building-to-building links, so protection is part of the design instead of an afterthought.
Wi-Fi, switching, firewalls and internet that hold up across a whole facility.
Call or text: 405-285-3845
New customers: start@unitycareit.com
Existing customers: support@unitycareit.com
Service area: based in Edmond, Oklahoma, serving Oklahoma, Texas and Kansas
Hours: Mon–Fri 8 AM–5 PM CT; 24/7 after-hours support